Operating voltage |
AC (85 ~ 260) V / 50/60 Hz |
Mains supply current limit |
1.5 A / AC 230 V |
Mains supply fuse |
4 A / AC 250 V slow blow (20 mm) |
Mains supply fault threshold voltage |
≤ AC 60 V |
Power supply |
2.2 A / DC 28 V |
Standby battery capacity |
(2 × DC 12 V) 7.2 Ah |
Maximum battery current draw |
1.5 A / maximum operating temperature |
Battery fuse |
6 A resettable (electronic fuse) |
Battery fault threshold voltage |
< DC 20 V |
Quiescent current |
110 mA / 28.5 V |
Addressable loops |
2 |
Number of connected devices per loop |
125 |
Loop current (max) |
400 mA |
Loop monitoring |
Open- and short-circuit |
Configurable audio/visual alarm groups (max) |
512 |
Conventional audio/visual alarm device driver |
800 mA |
Conventional audio/visual alarm end-offline resistor |
10 kΩ |
Alarm zone monitoring |
Open- and short-circuit |
Alarm zone voltage (max) |
DC 27.5 V |
Alarm zone fuse |
1.1 A resettable (electronic fuse) |
Number of programmable output relays |
2 |
Ancillary fire C/O relay |
2 x (1.0 A / DC 30 V / 1 A / AC 240 V) |
Ancillary fault N/C relay |
1.0 A / DC 30 V / 1 A / AC 240 V |
Auxiliary supply |
DC 28 V / 300 mA |
Evacuation start / stop input |
Non-latching, voltage-free |
Remote reset input |
Non-latching, voltage-free |
Number of networked panels |
4 |
Terminal wiring |
(0.4 ~ 2.5) mm2 |
Operating temperature |
(-5 ~ +40) °C |
Operating humidity |
(0 ~ 95) % RH, non-condensing |
Storage temperature |
(-25 ~ +80) °C |
Storage humidity |
(0 ~ 98) % RH, non-condensing |
Dimensions (h × w × d) |
(420 × 337 × 99) mm |
Weight (excluding batteries) |
4.0 kg |
Releasing Outputs
Pre-release delay time |
(0 ~ 30) s in 5 s intervals |
Number of programmable output relays |
6 |
Stage One contact rating |
1.0 A / DC 30 V / 0.5 A / AC 125 V |
Stage Two output |
Continuous or pulsing / 1 s on / 1 s off |
Stage Two contact rating |
1.0 A / DC 30 V / 0.5 A / AC 125 V |
Extinguishment release time |
(60 ~ 300) s in 5 s intervals or until Reset |
Extinguishment output 2 delay time |
(0 ~ 10) min in 1 min intervals |
Extinguishant released indication |
Immediate upon release or pressure switch input signal |
Released contact rating |
1.0 A / DC 30 V / 0.5 A / AC 125 V |
Aborted contact rating |
1.0 A / DC 30 V / 0.5 A / AC 125 V |
Reset inhibit time |
(0 ~ 30) min in 1 min intervals |
Extraction fan contact rating |
1.0 A / DC 30 V / 0.5 A / AC 125 V |
Earth fault monitoring |
Enabled / Disabled |
Fault output |
Enabled / Disabled |
Fault relay contact rating |
1.0 A / DC 30 V / 0.5 A / AC 125 V |
Auxiliary supply output (continuous) |
DC 30 V (max) / 200 mA |
Audio/Visual Alarms
Conventional audio/visual alarm device output |
1000 mA |
total Conventional audio/visual alarm endof- line resistor |
10 kΩ |
Alarm zone voltage (max) |
DC 30 V |
Electronic alarm zone fuse |
1 A |
Miscellaneous
Number of user interface languages |
2 |
Terminal wiring |
(0.4 ~ 2.5) mm2 |
Operating temperature |
(-5 ~ +40) °C |
Operating humidity |
(0 ~ 95) % RH, non-condensing |
Storage temperature |
(-25 ~ +80) °C |
Storage humidity |
(0 ~ 98) % RH, non-condensing |
Dimensions (h × w × d) |
(400 × 330 × 85) mm |
Weight (excluding batteries) |
4.3 kg |